EDPN SERVICES & SYSTEM · CRITICAL POWER SYSTEMS · VIETNAM
EDPN · Load Banks & Capacity Testing

EDPN 110LB120-T Battery Capacity Tester

10 – 240 Vdc, 0 – 120 A Constant Current DC Load Bank

LOAD BANKS & CAPACITY TESTINGEDPN
EDPN 110LB120-T Battery Capacity Tester — EDPN product image
EDPN PRODUCTSUPPLY · COMMISSIONING · SERVICE
OverviewFeaturesSpecificationsDownloadsEDPN projectsMore models
OVERVIEW

EDPN 110LB120-T Battery Capacity Tester.

Battery discharge testing is the direct method for evaluating the actual capacity of a battery group, because a constant-current discharge reproduces the working condition of the batteries under load.

Because DC power systems in industrial utilities use different battery voltage levels (24 V, 48 V, 110 V, 120 V, 220 V, 240 V), the 110LB120-T is built as an unattended, automatic instrument with intelligent stop points and wide voltage variability for almost all battery types.

FEATURES

Features & benefits.

Features

  • Wide range: supports 10 – 280 V battery groups (240/220 V at 60 A; 120/110 V, 96 V, 48 V, 24 V at 120 A; 12 V at 60 A).
  • 5.7 inch touch LCD displays all real-time data and graphs and supports direct click operation.
  • 4 adjustable stop points: group low voltage 0 – 280.0 V, discharge time 0 – 99 h 99 min, discharge capacity 0 – 9999 Ah, cell low voltage 0 – 15.00 V.
  • 3 discharge modes: constant current 0 – 120 A, constant power 0 – 18 kW, constant resistance 0.16 Ω – ∞.
  • Optional wireless modules monitor cell voltages during the test; each module monitors 4 batteries simultaneously.
  • Presetting function stores 8 sets of discharge parameters in advance to speed up repeat tests.
  • Non-volatile internal memory keeps records safe even on unexpected shutdown; review, delete or download via USB disk or RS232.
  • Extendable: with a current clamp the 110LB120-T works together with other EDPN LB-T units or external load units.

Protection

  • Input over-voltage — LCD prompt + beep
  • Reverse polarity — LCD prompt + beep
  • Overload — LCD prompt + beep
  • Overheat — LCD prompt + beep

Supplied with

  • Carry case 370 x 600 x 800 mm, 15 kg
  • Power cable 2 x 3 m, 50 mm²
  • AC power cord 1 x 3 wires x 1 mm²
  • User manual
  • USB disk
  • Current clamp (option) 100 A / 200 A / 600 A
SPECIFICATIONS

Technical data.

EDPN product data. Confirm the current datasheet and the project specification before selection.

Discharge ranges (voltage → current)

10 ÷ 15 V0 ÷ 60 A
21.6 ÷ 58 V0 ÷ 120 A
86 ÷ 140 V0 ÷ 120 A
180 ÷ 240 V0 ÷ 60 A
Max. extension current720 A max. (120 A internal + 600 A external)

Current measurement

Internal current range0 ÷ 120 A
Accuracy & resolution≤ ±0.5 %, 0.1 A
External current range0 ÷ 600 A (optional current clamp)
Accuracy & resolution≤ ±1 %, 0.1 A

Voltage measurement

Group voltage range10 ÷ 300 V
Accuracy & resolution≤ ±0.5 %, 0.1 V
Cell voltage range0 ÷ 15 V
Accuracy & resolution≤ ±0.5 %, 0.01 V

Power supply

Power supply voltage220 VAC (-20 % / +30 %)
Frequency50 / 60 Hz
Power consumption350 W (max)

Communication & storage

Communication portUSB / RS232
Internal memory8 Mbit Flash

CE certificate

LVD standards2006/95/EC: EN 61010-1:200
EMC standards2004/108/EC Annex II: EN 61000-6-1:2007, EN 61000-6-3:2007, EN 61000-3-2:2006+A2:2009, EN 61000-3-3:2008

Environment

Operating temperature-5 ÷ 50 °C
Storage temperature-40 ÷ +70 °C
Humidity5 % – 95 % RH
Altitudebelow 1000 m
Working noise< 60 dB (at 1 m)

Dimensions & weight

Main tester230 x 370 x 670 mm
Carrying case370 x 600 x 800 mm
Weight24 kg (main tester) / 46 kg (gross) / 0.3 kg (each wireless module)

Ordering information

110LB120-TBattery discharger & capacity tester
LB-ASPC analysis software
HEC-100A100 A current clamp
HEC-200A200 A current clamp
HEC-600A600 A current clamp
ED-24612Wireless module for 2 V / 4 V / 6 V / 12 V
ED-122Wireless module for 1.2 V / 2 V
DOWNLOADS

Datasheets & documents.

EDPN datasheet

The datasheet for this EDPN product is available on request.

REQUEST DATASHEET →
EDPN PROJECTS

Where EDPN has worked with this product.

ALL PROJECTS & REFERENCES →
BY SECTOR

Battery commissioning & capacity tests with EDPN DC load banks.

46 sites in EDPN’s reference list where EDPN installed, commissioned or capacity-tested batteries. Open a sector to see the sites.

Oil & Gas13 sitesFULL OIL & GAS REFERENCE LIST →
LNG & Petrochemical3 sitesFULL LNG & PETROCHEMICAL REFERENCE LIST →
Utilities11 sitesFULL UTILITIES REFERENCE LIST →
Transmission & Distribution15 sites
  • 2012–2024Tuy Ha 110kV S/SNhon Trach, Dong Nai
  • 2016–2018Toul Pongror 115kV S/S (GS8)Cambodia
  • 2015Dong Hoi 220kV S/SQuang Binh
  • 2011–2014An Phu 110kV GIS S/SSouthern Vietnam
  • 2014Pho Noi 500kV S/SHung Yen
  • 2013–2014Phu My 2 IZ 220kV S/SBa Ria – Vung Tau
  • 2014Thap Cham 220kV S/SNinh Thuan
  • 2013Binh Son 110kV S/SDong Nai
  • 2013Dong Hai 110kV S/SBac Lieu
  • 2013Phu Chau 110kV S/SAn Giang
  • 2013Thanh Phu 110kV S/SSouthern Vietnam
  • 2013Thap Muoi 110kV S/SDong Thap
  • 2013Thoai Son 110kV S/SAn Giang
  • 2013Vinh Thuan 110kV S/SKien Giang
  • 2012Binh Chanh 110kV S/SSouthern Vietnam
FULL TRANSMISSION & DISTRIBUTION REFERENCE LIST →
Industrial3 sitesFULL INDUSTRIAL REFERENCE LIST →
Railway & Transportation1 site
  • 2023Hanoi Metro Line 3 (Nhon – Hanoi Station)Hanoi
FULL RAILWAY & TRANSPORTATION REFERENCE LIST →
DC LOAD BANKS

More models in this range.

ALL 5 MODELS →
LIFECYCLE SERVICES

Lifecycle services for this product.

ALL SERVICES →
CONTACT EDPN

New project or installed equipment?

Send the specification for a new project, or equipment details for service support.