Features
- Wide range: supports 10 – 280 V battery groups (240/220 V at 60 A; 120/110 V, 96 V, 48 V, 24 V at 120 A; 12 V at 60 A).
- 5.7 inch touch LCD displays all real-time data and graphs and supports direct click operation.
- 4 adjustable stop points: group low voltage 0 – 280.0 V, discharge time 0 – 99 h 99 min, discharge capacity 0 – 9999 Ah, cell low voltage 0 – 15.00 V.
- 3 discharge modes: constant current 0 – 120 A, constant power 0 – 18 kW, constant resistance 0.16 Ω – ∞.
- Optional wireless modules monitor cell voltages during the test; each module monitors 4 batteries simultaneously.
- Presetting function stores 8 sets of discharge parameters in advance to speed up repeat tests.
- Non-volatile internal memory keeps records safe even on unexpected shutdown; review, delete or download via USB disk or RS232.
- Extendable: with a current clamp the 110LB120-T works together with other EDPN LB-T units or external load units.