Battery Services

Battery Capacity Testing

Constant-current discharge testing to IEEE 450, 1106 and 1188 — the most reliable way to prove the real capacity of a battery.

LIFECYCLE SERVICESB · SPECIALIST
EDPN VIETNAMENGINEERING · TESTING · COMMISSIONING · SERVICE
SCOPE

What EDPN does.

Impedance and resistance testing is useful for trending, but a constant-current discharge test is the direct way to measure the capacity a battery will actually deliver under load.

Per IEEE recommended practice, the interval is 5 years for vented Ni-Cd (IEEE 1106), no more than 25% of the expected service life for vented lead-acid (IEEE 450), and no more than 25% of the service life or 2 years, whichever is less, for VRLA (IEEE 1188) — moving to annual tests once a battery shows capacity loss.

EDPN performs the test with its own DC load bank fleet — 48 V to 240 V, up to 300 A, with per-cell voltage monitoring during discharge — and issues a report with the discharge curve, per-cell behaviour, measured capacity against rated capacity, and the cells that should be replaced.

Because the equipment is EDPN's own and held in Vietnam, testing can be scheduled around your outage window rather than around an import.

EDPN Services & System is an authorised service partner for Chloride and Alcad in Vietnam.