Power generation plantsTransmission and Distribution substationsContinuous process industriesOil & Gas and Petrochemical industriesRail transport
FEATURES
Features & benefits.
Key advantages
User friendly Large color touch screen with 2000-event exportable log.
USB access Export of all the recorded events using USB flash drive. Memorization of complete electronic settings for future maintenance needs.
Batteries compatibility Innovative full integration with SMC/Salt Batteries (Sodium Metal Chloride Batteries). Full compatibility with Lead-acid, nickel-cadmium batteries, sealed or vented and Lithium-Ion.
Life time Designed for 20+ years of continuous operation with appropriate maintenance plan.
Inrush current Reduced ≤ 10xIn to avoid oversizing upstream protection and 2-step strat-up.
VIDEO
CP70R options.
The video is loaded from YouTube (youtube-nocookie.com) only after you press play. Google may then receive your IP address and set cookies under its own policy — see our Cookie Policy.
SPECIFICATIONS
Technical data.
Summarised from the manufacturer’s published data. Confirm the current datasheet and the project specification before selection.
Input
AC voltage
Single phase 1 x 230 V (220, 240)
Three phase
3 x 400 V (380, 415)
Voltage tolerance
+/- 10 %
Neutral configuration
Any configuration, with or without neutral
Frequency
50 Hz (60 Hz)
Frequency tolerance
+/- 5 %
Frequency range (temporary)
45 Hz to 65 Hz (with 50 Hz nominal)
Total harmonic current distorsion (THDI)
< 34 % (6-pulse version)< 34 % (6-pulse version)
Inrush current
< 15 x In (for 6-pulse and 12-pulse)
Output
Nominal DC voltage
24...400V
Output DC voltage range
17...550 V
Voltage stability (in stabilized floating mode, input within tolerance)
Unitary system +/-1 %
Parallel systems
+/-1 % to +/-2 %
Voltage ripple
≤ 1 % RMS, in float mode, battery disconnected
Current limitation
I nominal
Battery
Type
Salt Metal Chloride, Lead acid or nickel cadmium, vented or recombination
Autonomy
From few minutes to several hours, on request
Battery current limitation (typical, float, & boost modes)
0.1 C (lead-acid battery) / 0.2 C (nickel-cadmium battery)
General data
Operating temperature
0 to 40 °C (-20°...55°C on request)
Storage temperature
-20 to +70 °C
Relative humidity
< 95 % non condensing
Operating altitude
1000 m max without derating
Cooling
Natural convection on most of the range
Efficiency
Up to 96 % according to rating
External protection
IP 20 according to IEC 60529
Internal protection
Protection against unintentional direct contacts, as per IEC 60950-1