Oil & Gas industries, offshore and onshoreRefining and petrochemical plantsPower generation plantsRail transportProcess industries
FEATURES
Features & benefits.
Key advantages
Maintainability The easiest on the market with total components front access.
Reliability Innovative internal temperature reduction, through dual redundant cooling channels. Multiplied redundancy with Chloride® Patented Smart Parallel Switching function that dynamically controls paralleled systems.
User friendly Large color touch screen with 2000-event exportable log.
USB access Export of all the recorded events using USB flash drive. Memorization of complete electronic settings for future maintenance needs.
Batteries compatibility Innovative full integration with SMC/Salt Batteries (Sodium Metal Chloride Batteries). Full compatibility with Lead-acid, nickel-cadmium batteries, sealed or vented and Lithium-Ion.
Low THDi 6 - or 12-pulse thyristor rectifier. Down to 5% THDI in 12-pulse SCR system with harmonic filters.
Life time Designed for 20+ years of continuous operation with appropriate maintenance plan.
VIDEO
CP70Z presentation.
The video is loaded from YouTube (youtube-nocookie.com) only after you press play. Google may then receive your IP address and set cookies under its own policy — see our Cookie Policy.
SPECIFICATIONS
Technical data.
Summarised from the manufacturer’s published data. Confirm the current datasheet and the project specification before selection.
Input
AC Voltage
3 X 400 V (380, 415) (other available on request)
Voltage Tolerance
+/- 10%
Frequency
50 Hz (60 Hz)
Frequency Tolerance
+/- 5%
Inrush current
≤ 10 x ln (other available on request)
Output
AC Voltage Single phase
1 x 230 V (220, 240) ; 1 x 110 V (115, 120) (other available on request)
AC Voltage Three phase
3 x 400 V (380, 415) ; 3 x 220 V (200, 208, 230) (other available on request)
Frequency
50 Hz (60 Hz)
Frequency stability with internal oscillator
+/- 0.05%
Frequency stability with reserve synchronism
+/- 3 % (from 1 to 5% adjustable)
Voltage stability (for 0 to 100 % load variation): Dynamic
VFI SS 111 as per IEC/EN 62040-3, class 1
Inverter overload capability: 1 minute
150 % of nominal power
Inverter overload capability: 10 minutes
125 % of nominal power
Short circuit clearance (in % of nominal current): 1-ph output
250 % / 100 ms - 175 % / 5s
Short circuit clearance (in % of nominal current): 3-ph output Ph-N
315 % / 100 ms - 220 % / 5s
Short circuit clearance (in % of nominal current): 3-ph output Ph-Ph
190 % / 100 ms - 135 % / 5s
Harmonic voltage distortion: With 100% linear load
< 3%
Harmonic voltage distortion: With 100% non-linear load
SS as per IEC/EN 62040-3
Allowable power factor
0.5 lagging to 0.5 leading
Battery
Battery
Salt Metal Chloride, Lead acid or nickel cadmium, vented or recombination
Autonomy
From few minutes to several hours, on request
Battery current limitation (typical, float, & boost modes)
0.1 C (lead-acid battery) / 0.2 C (nickel-cadmium battery)
General Data
Operating temperature
0 to 40 °C (-20°...55°C on request)
Storage temperature
-20 to +70°C
Relative humidity
< 95% non condensing
Operating altitude
1000m max without derating (other available on request)
Cooling
Forced ventilation
Efficiency
Up to 90% according to rating
External protection
IP 20 according to IEC 60529 (other available on request)
Internal protection
Protection against unintentional direct contact, as per IEC 60590-1/62477-1