EDPN SERVICES & SYSTEM · CRITICAL POWER SYSTEMS · VIETNAM
Chloride · Hazardous-Area Critical Power

XP90R DC UPS - ATEX/IECEx

Smallest on the market, Chloride® XP90R is an industrial rectifier / battery charger explosion proof Zone 1 & 2.

UPS TypeDC UPS ATEX/IECEx
Rating<33 kW
TechnologySCR
HAZARDOUS-AREA CRITICAL POWERCHLORIDE
XP90R DC UPS - ATEX/IECEx — manufacturer product image
MANUFACTURER PRODUCT IMAGESUPPLY · COMMISSIONING · SERVICE
OverviewFeaturesVideoSpecificationsDownloadsMore models
OVERVIEW

XP90R DC UPS - ATEX/IECEx.

APPLICATIONS
Offshore production process in Explosion-risk areasWellhead platforms / Unmanned platformsPipelines instrumentationRefineries
FEATURES

Features & benefits.

Key features

  • Small footprint High power DC UPS system available in small size to optimize space on offshore platform.
  • Optimized thermal management Uses Chloride’s patented Exd enclosure cooling system.
  • Strong immunity to perturbations Integrates an isolating input transformer.
  • Safe control, door closed Allows the user to operate the switches, circuit breakers, and control buttons door closed.
  • Smart access to UPS data Large graphical user interface on the front. Software update and configuration of parameters through PC with PPVIS software. Embedded event logger (up to 2000 events) Close range Wi-Fi module - To download the event logger without opening the equipment enclosure.
  • Safe and easy maintenance Once open, the front door gives direct access to all components.
VIDEO

Example of a Chloride explosion-proof UPS solution.

The video is loaded from YouTube (youtube-nocookie.com) only after you press play. Google may then receive your IP address and set cookies under its own policy — see our Cookie Policy.

SPECIFICATIONS

Technical data.

Summarised from the manufacturer’s published data. Confirm the current datasheet and the project specification before selection.

Input

AC Voltage3 x 400 V (380, 415)
Voltage tolerance+/- 10%
Frequency50 Hz (60 Hz)
Frequency tolerance+/- 5%

Output

DC voltage (nominal)24 / 48 / 110 / 125 / 220 / 400V
Voltage stability (Input within tolerance)+/- 1% in float mode +/- 1.5% for parallel rectifiers
Voltage ripple0.1 RMS, in float mode, battery connected
Current limitationI nominal / up to 150% for 1 minute
Charging characteristicsIU according to DIN 41773

Battery

BatteryValve Regulated Lead Acid (VRLA) Recombinaison Nickel Cadmium
AutonomyFrom few minutes to several hours, as per customer’s requirement
Battery current limitation (typical, float, mode)0.1 (Lead Acid or Nickel Cadmium battery)
Battery temperature compensation-3 mV / °C / cell

General Data

Operating temperatureUp to 55°C
Relative humidity100% condensing
Operating altitude1000m max without derating
CoolingNatural
EfficiencyUp to 90% according to rating and configuration

Enclosure

DesignATEX/IECex certified for Zone1, II 2G Ex d IIB+H2 T3 (IEC 60079)
MaterialStainless steel (SS316L), Carbon steel (mild steel) or Aluminum
External ingress protectionIP 66 according to IEC 60529
DimensionsVarying according to ratings & options
DOWNLOADS

Datasheets & documents.

Product information source: Chloride — official product page ↗. Specifications and documents belong to the manufacturer and may change; EDPN confirms the configuration for each project.

HAZARDOUS-AREA DC UPS

More models in this range.

ALL 2 MODELS →
CONTACT EDPN

New project or installed equipment?

Send the specification for a new project, or equipment details for service support.