EDPN SERVICES & SYSTEM · CRITICAL POWER SYSTEMS · VIETNAM
Chloride · Hazardous-Area Critical Power

XP20R DC UPS - ATEX/IECEx

Chloride® XP20R is an industrial rectifier / battery charger explosion proof Zone 1 & 2 developed specifically for offshore environment & tough operating conditions. It is the smallest DC UPS of XP range.

UPS TypeDC UPS ATEX/IECEx
Rating<1800W
TechnologySMR
HAZARDOUS-AREA CRITICAL POWERCHLORIDE
XP20R DC UPS - ATEX/IECEx — manufacturer product image
MANUFACTURER PRODUCT IMAGESUPPLY · COMMISSIONING · SERVICE
OverviewFeaturesVideoSpecificationsDownloadsMore models
OVERVIEW

XP20R DC UPS - ATEX/IECEx.

APPLICATIONS
Offshore production process in Explosion-risk areasWellhead platforms / Unmanned platformsPipelines instrumentationRefineries
FEATURES

Features & benefits.

Key features

  • Small footprint To optimize space on offshore platform.
  • Durability Optimized thermal management.
  • Immunity Strong immunity to perturbations.
  • Safe control, door closed Allows the user to operate the switches, circuit breakers, and control buttons door closed.
  • Smart access to data Large graphical user interface on the front.
  • Safe and easy maintenance Once open, the front door gives direct access to all components.
  • Alarms Embedded event logger (up to 2000 events). Close range Wi-Fi module - To download the event logger without opening the equipment enclosure.
VIDEO

Example of a Chloride explosion-proof UPS solution.

The video is loaded from YouTube (youtube-nocookie.com) only after you press play. Google may then receive your IP address and set cookies under its own policy — see our Cookie Policy.

SPECIFICATIONS

Technical data.

Summarised from the manufacturer’s published data. Confirm the current datasheet and the project specification before selection.

Input

AC Voltage1 x 230 V (220, 240)
Voltage tolerance+15% / -18% (187 V to 264 V)
Frequency50 Hz (60 Hz)
Frequency rangeFrom 47 Hz to 63 Hz
Total harmonic current distortion (THDi)≤ 5%
Inrush current≤ 10 x In
Input power factor≤0.95

Output

Nominal DC Voltage24 V / 48 V
Output DC voltage range+/-15 %
Static regulation+/-1 %
Voltage ripple≤ 0.1 % RMS (disconnected battery)
Current limitationI nominal
Charging modeWith valve regulated lead acid: single charge mode With recombination nickel cadminum: single charge mode (recommended) or dual charge mode
Charging currentWith valve regulated lead acid: 0.05C10 to 0.1C With recombination nickel cadmium: 0.1C (up to 0.2C subject to battery enclosure certification limits)

Protections

InputType: MCCB Breaking capacity: 18 kA Lightning arrestor / spike suppressor
BatteryPre-heating start-up Type: MCCB Breaking capacity: 18 kA Battery reverse polarity protection Low Voltage Disconnection (LVD) device External battery cut-off
OutputType: MCCB Breaking capacity: 18 kA
Isolation VoltageInput / output: 4200 Vdc / 1 min Input / ground: 2300 Vdc / 1 min Output / ground: 1500 Vdc / 1 min
SystemInternal anti-condensation paint Conformal coating of Printed Circuit Boards (PCB) Volatile Corrosion Inhibitot (VCI) for 2 years

Battery

TypeValve regulated lead acid
AutonomyFrom few minutes to several hours, upon requirement

Ratings

Output voltage24 Vdc 48 Vdc
Output current24 Vdc ==> 15, 25, 50A 48 Vdc ==> 15, 25 A

General Data

ExecutionII 2 G Ex db eb IIB+H2 T5 Gb IP66
External ingress pprotectionIP 66
Rectifier efficiencyFrom 86 % (24 V) to 89 % (48 V)
Operating temperatureFrom 0 °C to 50 °C (external temperature, without derating)
Storage temperatureFrom -20 °C to +70 °C (battery excluded)
Relative Humidity100 %, condensing
Operating Altitude1000 m (without system derating)
CoolingNatural convection
Noise≤ 30 dB (at 1m in front of the unit)
DimensionsW: 490 mm / D: 491 mm / H: 1200 mm
WeightVarying according to ratings and options
InstallationVertically wall-mounted
Design life20 years
MaterialsCharger enclosure: Ex d, copper-free marine grade aluminum Customer terminal box: Ex e, stainless steel 316L Supporting frame: C35 steel
PaintingExternal: C5 marine-grade painting, RAL 7035 or 7032Internal: Hygroscopic orange RAL 2004
Customer connectionThrough pre-dilled gland plate, 1.5mm thickness

Standards

StandardsIEC EN 60146-1-1:2009 IEC EN 61000-6-2:2006 IEC EN 61000-6-4:2007 AMD1:2011 IEC EN 61439-1:2011 IEC EN 60529:1989 AMD1:1999 NFC 58-311:1990 IEC EN 60079-0 IEC EN 60079-1 IEC EN 60079-7
DOWNLOADS

Datasheets & documents.

Product information source: Chloride — official product page ↗. Specifications and documents belong to the manufacturer and may change; EDPN confirms the configuration for each project.

HAZARDOUS-AREA DC UPS

More models in this range.

ALL 2 MODELS →
CONTACT EDPN

New project or installed equipment?

Send the specification for a new project, or equipment details for service support.