Chloride® CP70i DC/AC Inverter
Battery Monitoring System (BMS) - ATEX/IECEx
Innovative SMC/Salt Batteries & UPS Integration
Battery Monitoring System (BMS) - ATEX/IECEx
Single Cell MC/MB NiCad battery
Single Cell LCE / LB NiCad battery
Single Cell HC/ HB NiCad Battery
CleverWatch™ advanced NiCad battery remote monitoring solution
UPS Adapter CS141 Professional
UPS Adapter CS141 Budget / Budget LC
UPS Adapter CS141 HW161 Update
BAS - Battery Analyse System (On Demand)
For Manufacturers: SMARTBATTERY
EDPN IBAD-2612-ED Intelligent Battery Charge & Discharge Unit
EDPN 110LB120-T Battery Capacity Tester
EDPN 220LB300-T Battery Capacity Tester
EDPN 220LB150-K Battery Capacity Tester
EDPN 110LB300-K Battery Capacity Tester
EDPN 48LB150-K Battery Capacity Tester
Designed to provide a simple, fast and cost effective solution for DC power requirements .
DC UPS / Natural cooling
24 ÷ 125 Vdc | 10 ÷ 250 A
SCR
Key advantages |
|
More reliable |
Thanks to the proven thyristor technology that Chloride® has mastered for over 70 years |
More robust |
With a natural cooling design throughout the range. No risk of fan-related failures |
Less maintenance |
Due to the use of long-life components |
Easier to use |
With its human-machine interface featuring a large, high-contrast display. The display shows the rectifier diagram and indicates any faults, which are also indicated by summary LEDs |
Faster availability |
Thanks to its design in 100% industrialized configurable sub-assemblies. The Chloride® FP50R charger-rectifier can be available in only 6 to 8 weeks |
Range |
|
1-Phase |
10/25/40/60/100 Adc |
3-Phase
|
25/40/60/100/160/250 Adc |
Input |
|
Rated voltage |
1-Phase: 230Vac (220,240) 3-Phase: 400Vac (380,415) / 208Vac |
Input voltage tolerance |
± 10% |
Frequency |
47Hz / 63Hz
|
Frequency tolerance |
± 5% |
Inrush current |
1-Ph: < 15 ln 3-Ph: < 10 ln |
Output |
|
Rated voltage DC |
24V (17V-34V), 48V (34V-68V), 110-125V (88V-179V) |
Voltage stability (in stabilised floating mode, input within tolerances) |
Single system: ± 1% Dual system: ± 1% to ± 2% |
Voltage ripple rate |
≤ 5 % at 100 % load |
Battery |
|
Type | Lead acid or nickel cadmium, vented or recombination |
Autonomy | From few minutes to several hours, as required |
24V – Number of battery cells |
Lead-Acid: 12 NiCd: 18 – 20 |
48V – Number of battery cells |
Lead-Acid: 24 NiCd: 36 – 44 |
110V – Number of battery cells |
Lead-Acid: 54 NiCd: 82 – 92 |
125V – Number of battery cells |
Lead-Acid: 60 NiCd: 91- 105 |
Battery current limitation (typical, float, & boost modes) |
0.1 C (lead-acid battery) / 0.2 C (nickel-cadmium battery) |
General Data |
|
Rectifier technology |
SCR, 2-pulses thyristors |
Operating temperature |
From 0 to 40 °C (without system derating) |
Storage temperature |
From -20 °C to +70 °C (battery excluded) |
Relative humidity |
< 95 % non condensing at 20 °C |
Operating altitude |
1000m (2) (without downgrading the system) |
Cooling |
Natural convection |
External ingress protection |
IP21 to IEC 60529 (other protection classes available: IP41 / IP42) |
Internal protection |
Protection against unintentional direct contact according to IEC 62477-1 |
Noise (at 1m in front of the unit) |
≤ 60 dB |
Cable entry |
Bottom (Top on Request) |
Frame colour |
RAL 7035 or RAL 7032 |
Dimensions |
Varies according to size and options |
Monitoring
|
|
Local, on the front panel | Graphic display with navigation buttons (75mm x 45mm) |
List of relay alarms | Standards: general alarm, mains failure, battery charging, end of discharge Options: ground fault, boost mode, overvoltage, undervoltage |
Alarm relays, contact characteristics |
Changeover contact, switching capacity in accordance with DIN VDE 0660/IEC 60947: 1 A (24 V (DC13)), 0.2 A (110 V, DC13), 0.1 A (220 V, DC13) 3 A (24 V, AC15), 3 A (120 V, AC15), 3 A (230 V, AC15) |
Remote control (optional) |
RS485, TCP-IP, IEC 61850, SNMP, PROFIBUS |
Standards
|
|
IEC 61000-6-2 : 2016 |
Electromagnetic compatibility (EMC) – Part 6-2: General requirements – Emission for industrial environments |
IEC 61000-6-4 : 2018 |
Electromagnetic compatibility (EMC) – Part 6-4: Generic standards – Emission for industrial environments |
IEC 61000-6-5 : 2015 |
Electromagnetic compatibility (EMC) – Part 6-5: Generic standards – Emission for equipment used in power plant and substation environments |
IEC 62477-1 : 2022 |
Safety requirements for electronic power conversion systems and equipment – Part 1: General |
IEC 60146-1-1 : 2009 |
Semiconductor converters – General requirements and mains switched converters – Part 1-1: Specification of basic requirements |
IEC 60529 : 2013 |
Degrees of protection provided by the enclosures (IP Code) |
Copyright © 2023 EDPN Services & System Co., Ltd by A&B Viet Nam. All Rights Reserved.
Please leave your requirement, we will get back to you shortly