STANDARD FEATURES:

• Sinusoidal absorption.

• High efficiency.

• Compact size.

• High reliability.

• Remote EPO.

• Adjustable WALK-IN and DIESEL MODE (to minimize the impact on the output).

• Multilingual front display.

• Slot-in SNMP adapter.

• Dynamic parallel.

• Dynamic ON-LINE technology/ ECO Mode.

• Wide range of additional options to meet the specific requirements of the plant (isolation transformers, synchronization box for parallel systems, monitoring interfaces, etc.)

THETYS EVO 60 - 80 - 100 - 125 - 160kVA

3Ph(In) – 3Ph(Out)

Model

Thetys EVO 60KVA

Thetys EVO 80KVA

Thetys EVO 100KVA

Thetys EVO 125KVA

Thetys EVO 160KVA

Nominal output power (0.9 PF)

60KVA

80KVA

100KVA

125KVA

160KVA

54KW

72KW

90KW

112.5KW

144KW

Input

Voltage (Vac)

400 (-20%/ + 15%); 380/415 selectable

Frequency (Hz)

50 - 60 (± 5%)

Power Factor

>0.99

Harmonic Distortion (THDi)

< 3%

Output

Voltage (Vac)

380 - 400 - 415 (selectable)

Frequency (Hz)

50/ 60 (selectable)

Harmonic Distortion (THDv)

< 1% for linear load, < 5% for non-linear load

Phase

Three Phase

Waveform

Pure Sine Wave

Efficiency (DC : AC)

>95%

Protection

Overload Protection

UPS automatic power off if overload exceeds 125% for 10mins or >200% for 100 milliseconds

Short Circuit Protection

UPS output cut off immediately or protected by input fuse or circuit breaker

Alarm

Buzzer beeps under backup mode, battery fault and UPS fault.

Battery

Type

External only

Typical recharge time

8 hours to 90%

Protection

Wall mounted fuses switch box

Standards

Marking

IEC EN 62040-2

Safety

IEC EN 62040-1

EMC

IEC EN 62040-2

Test and Performance

IEC EN 62040-3

Quality

ISO 9001:2008

General

Dimension (WxDxHmm)

815 x 865 x 1705

Product Weight (kg)

570

600

630

662

720

Display (LED)

Line mode (Green), Bypass/Battery mode (yellow), Fault (red)

Display (LCD)

Input/Output voltage and frequency, On-line mode, Backup mode, Battery capacity, Load level

Communication Interface

RS232/ USB/ RS485 (Modbus)/ RJ45 (SNMP)

Audible noise

< 60db

Ambient Temperature (°C)

0 to 40

Storage Temperature (°C)

-10 to +70

Humidity

< 95, Non-Condensing

Subject to changes without notice

Astrid Thetys 60KVA - 160KVA Rev01
OMD10008 - Technical specification Thetys EVO 60-80-100-125-160kVA
OMD10010 - Thetys EVO operating manual
For further information, please kindly contact us
Tel: +84 4 3726 4905
Email: [email protected]

3Ph(In) – 3Ph(Out)

The Thetys 60 – 160 kVA utilises double online conversion architecture with inverter transformer, offers galvanic isolation between the continuous and alternate line guaranteeing excellent dynamic response performance.

The IGBT rectifier with innovative sinewave input enables the reduction of input harmonics (THDi < 3%) and a power factor of the input ac near to unity (>0.99).

This characteristic makes the Thetys highly compatable with the installation upstream of the UPS without having to install additional filters.

The Thetys allows reduced costs for the most sophisticated data centres due to its compact dimensions and to its efficient design that enables an efficiency of over 94% to be achieved. It is possible to put the unit on the wall and side by side with other panels without losing performance due to a well designed cooling system.

The UPS has a user-friendly interface with synoptic panel and LCD display and includes a wide range of connection options that simplifies the use and control in the installations.

The Thetys is available in parallel configuration for redundancy and for power parallel. Installation is easy using parallel-ready technology that is included in the standard unit.