• On-line double conversion

• Output isolating transformer

• Automatic and manual by-pass

• Two-way static switch

• Automatic battery test

• Inverter Igbt technology with high frequency commutation

• Capability of supplying highly distorted loads with high crest factor

• High immunity to external disturbances

• RS232 - RS485 serial interfaces

• High instantaneous overload capability

• Automatic by-pass with high overload capability

• Very robust thanks to steel cabinet, frame and supports

• High MBTF (>150.000 H)

• Low MTTR (< 0.5h)

• Technology created for power plants and off-shore platforms on all product lines

• High efficiency starting at 25% load with low operating costs

• Easy installation and maintenance; total accessibility from the front

• Small footprint

• Easy to use and manage, with guided start-up and state-of-the-art diagnostics

• SNMP /MOD-BUS / REMOTE PANEL

• Control and visualisation software for Windows

• Teleservice available

TECHNICAL DATA SHEET “PLANET EVO E”

3Ph(In) – 1Ph(Out)

POWER (KV A)

20 30 40

UPS typology

ON LINE – Double Conversion

Nominal output power @ P.F. 0,8 (kVA)

20 30 40

Nominal output power @ P.F. 1 (KW)

16 24 32

Efficiency AC ÷ AC (%)

>90 >90 >90

Heat dissipation at nominal load and voltage:

- KW - Kcal

1,78 2,67 3.56 1531 2296 3062

UPS ambient temperature (°C)

0÷40

BATTERY ambient temperature (°C)

0 ÷ +25

UPS storage temperature (°C)

-10 ÷ +70

BATTERY storage temperature (°C)

-10 ÷ +60

Relative humidity non condensing (%)

<95

Altitude (mt)

<1000 (Above See Level)

Power derating for altitude > 1000mt

According “EN50091-3”

V entilation

FORCED

Requested cooling air volume (mt3/h)

700 800 900

Audible noise level (according EN 50091)

<58db

Standard battery type lead acid (N° cells)

192 192 192

Storage time of battery without recharge (at 25°C)

3 months

Protection degree

IP 20

EMC Compatibility

According to “EN 50091-2”

Paint

RAL 5026 Met. RAL 9006 Met.

Accessibility

Front and top access for service

Static load without battery (Kg/m2)

630 655 680

Input/output cable connection

Bottom Side

Transport

Base provided for forklift handling

Transport mechanical stress

According to “EN50091-1”

Design standard

According to “EN50091-1”

Free contact interface

On request

Serial communication interface

RS232-RS485

Parallel configuration

To increase output power up to 6 UPS or 5+1 redundant

Subject to changes without notice

For further information, please kindly contact us

Tel: +84 4 3726 4905

Email: [email protected]

PLANET E 20-40kVA

3Ph(In) – 1Ph(Out)